Products

Products

Battery Charger >> Conventional Charger

Use for General application

 

INPUT

Nominal Voltage
Voltage Range
Frequency
Input Current
Power Factor
Efficiency
Dielectric Strength
230 VAC, Single Phase
150 - 275 VAC
47 –53 Hz
<20A RMS
0.98 MIN.(50% Load to 100% Load)
6 88%
1.5 KV AC (I/P to O/P & Case)
   

OUTPUT

 
Nominal Voltage
Output Voltage Span Adjustment
Output Current
Power
Net Regulation
Ripple
Psophometric
Audible Noise
Battery Current Limit
Battery Protection
24 VDC
24V - 28V
2 X 50A (MAX.)
2 X 1400W (MAX.)
±0.5V load and line
< 200mV p –p
< 4mV
< 50 dBA
0.1AH of Battery Capacity
LVD (21-22V)
   

MECHANICAL

 
Weight
Dimensions
Enclosure
Input Connection
Output Connection
Approx. 25 Kgs.
280 (H) x 466 (W) x 480 (D) mm
IP-20, CRC Sheet, Powder coated Case,
Table top or 19” Rack Mounting
Stud Terminals
Stud Terminals
   

ENVIRONMENT

 
Operating Temperature
Storage Temperature
Cooling
Humidity
0º to 50º C
-10º C to +70º C
Convection
< 95% RH
Modular Systems, easy for Maintenance
Hot Plug-In Modules
Wide Input Voltage Range
Active Current Sharing
Potential Free Contacts for Remote Fault Annunciation
Power Factor Correction
Input High Voltage Disconnect (HVD) & Battery Low Voltage Disconnect(LVD)
Analog Controllers- Replaceable and Standby
Common O/P Voltage Control
Battery Current Limiting for each battery path (Presettable to suit battery Capacity).

ALARMS LED DISPLAY

FUNCTION MONITORING DISPLAY

1. AC FAIL
2. Battery Low
3. AC ON Battery discharge
4. Battery Reverse
5. Module Fail
6. LOAD ON
7. Battery ON
8. System On Float
9. System On Charge
LED DPM provided for-
1.Battery Voltage
2. Load Voltage
3. Battery Current
4. Load Current